edurant.com > MSOE > SEED > Final > Appendix L: User's Manual

Note: These instructions are revised from those originally submitted.

Appendix L: User's Manual

Description

The Push-Button Power supply has three different power supply units: a variable 35V unit, a fixed 15V unit, and a fixed +5V unit. Each unit is separately fused, and completely independent. The variable unit can be set to output a desired voltage or current, and is constantly monitored to ensure proper operation. The fixed units are monitored to provide constant voltage.

Instructions

Turning the unit on and off

Enabling and disabling the output

Setting a voltage or current

A voltage or current can be set for the variable supplies any time the power supply is on. The settings only take effect while the outputs are enabled (see "Enabling the output.") If too high a voltage is requested by the user the variable supply will output the maximum rated voltage. If too high a current is requested by the user, the variable supplies will return an error message (see "Resolving Errors.") A load must be present on both the positive and negative half of the variable supply before attempting to set a current or error conditions will occur.

Handling Errors

Four errors can occur on the power supply: over voltage, under voltage, over current, under current. Whenever an error occurs the outputs are automatically disabled. An error message will appear on the display and the warning light will come on. The error message is shown in Figure 15.

Figure 15: Example Error Message
Variable 1 - Negative polarity
OVER VOLTAGE
Press CLEAR to change settings,
or START/STOP to try again.

The error message will include the affected supply (VARIABLE 1, FIXED +/-15, FIXED +5), the effected polarity (POSITIVE, NEGATIVE), and the proper error (OVER VOLTAGE, UNDER VOLTAGE, OVER CURRENT, UNDER CURRENT) in the displayed message. Over voltage errors are often a result of too high an impedance for the supply to generate the desired current through, or else an internal problem has developed in the supply. Under voltage errors imply that the fixed supplies are being used with too low an impedance. Over current errors often indicate a short circuit or low impedance situation for the variable supply. Under current errors suggest that an internal error has occurred in the supply.

Troubleshooting

Table 13: Troubleshooting
Problem Things to check
Display not on when unit is turned on.
  • Check for blown fuses. The fuse panel is located ___.
  • Ensure the unit is plugged in.
Errors repeatedly occur and attached circuit has been verified as working.
  • Check for blown fuses. The fuse panel is located ___.
  • Check connections to the supply output. Make sure a load is connected to both halves of the variable supply if trying to control the supply via a current setting.

Any other problems, and these problems if not resolved by following the suggestions, should be referred to trained personnel.

Electrical Specifications

Table 14: Electrical Specifications
  +5 Volt +15 Volt -15 Volt +Variable -Variable
Output Voltage 5V dc +15Vdc -15Vdc 0 to +35Vdc 0 to -35Vdc
Output Current 2A 2A 2A 2A 2A
Ripple @ 1Amp 5mV 10mV 10mV 20mV@+35V 20mV@-35V
Input Fuse Rating 1A 1.5A 1.5A 4A 4A
AC Line Voltage 115Vac@60Hz        
AC line Fuse 10A        
Operating Temp. 30 to 100°F